FLUKE 1623-2 KIT F1623-2 GEO Earth Ground Tester

From £3104.99
  • Color:

Categories:

Buy With Confidence

100% Safe Payment


;

  • Description

    FLUKE 1623-2 KIT F1623-2 GEO Earth Ground Tester

    Feature:

    3- and 4-pole Fall-of-Potential, earth resistance loop testing

    4-pole Soil Resistivity testing

    Selective earth ground rod testing using 1 clamp

    Stakeless earth ground rod testing using 2 clamps

    IP56 rated for outdoor use

    Rugged carrying caseUSB data storage and transfer

    General Specifications

    Display: 1999 digit LCD

    Display with special symbols, digit height 25 mm, fluorescent backlight

    User interface

    Instant measurement through TURN and START one button concept. The only operating elements are rotary switch and START button

    Robust, water and dust resistant

    Instrument is designed for tough environmental conditions (rubber protective cover, IP56)

    Memory

    Internal memory storage up to 1500 records accessible via USB port

    Temperature Range

    Operating temperature

    -10°C to 50°C (14°F to 122°F)

    Storage temperature

    -30°C to 60°C (-22°F to 140°F)

    Temperature coefficient

    ±0.1% of reading/°C < 18°C > 28°C

    Intrinsic error

    Refers to the reference temperature range and is guaranteed for 1 year

    Operating error

    Refers to the operating temperature range and is guaranteed for 1 year

    Climatic class

    C1 (IEC 654-1), -5°C to +45°C (23° to +115° F), 5% to 95% RH

    Protective type

    IP56 for case, IP40 for battery door according to EN60529

    Safety

    Protection by double and/or reinforced insulation. max. 50 V to earth. IEC61010-1: Pollution degree 2

    EMC (emission immunity)

    IEC61326-1: Portable

    Quality system

    Developed, designed and manufactured according to DIN ISO 9001

    External voltage

    V ext, max = 24 V (DC, AC < 400 Hz), measurement inhibited for higher values

    V ext rejection

    > 120 dB (162⁄3, 50, 60, 400 Hz)

    Measuring time

    Typical 6 seconds

    Max. overload

    250 V rms (pertains to misuse)

    Auxiliary power

    6 x 1.5 V Alkaline (type AA LR6)

    Battery life span

    Typical > 3,000 measurements

    Dimensions (W x H x D)

    250 x 133 x 187 mm (9.75 x 5.25 x 7.35 in)

    Weight

    1.1 kg (2.43 lb) including batteries
    7.6 kg (16.8 lb) incl. accessories and batteries in carrying case

    RA 3-Pole Ground Resistance Measurement (IEC 1557-5)

    Switch position

    RA3-pole

    Resolution

    0.001 Ω to 10 Ω

    Measuring range

    0.020 Ω to 19.99 kΩ

    Accuracy

    ±(2% rdg + 3 d)

    Operating error

    ±(5% rdg + 3 d)

    Measuring Principle: Current/Voltage Measurement

    Measuring voltage

    Vm = 48 V AC

    Short-circuit current

    > 50 mA

    Measure frequency

    128 Hz

    Probe resistance (RS)

    Max 100 kΩ

    Auxiliary earth electrode resistance (RH)

    Max 100 kΩ

    Additional error from RHand RS

    RH[kΩ]•••RS[kΩ]/RA[Ω]•••0.2%

    Monitoring of RSand RHwith error indicator.
    Automatic range selection.
    Measurement is not performed if the current through the current clamp is too low.

    Notes:Shipping company does not accept liquids and powders and dry batteries